Connecting to a normally-open contact – HP Parallel Uninterruptible Power System User Manual

Page 46

Advertising
background image

UPS installation 46

WARNING:

To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11, a

UPS installed in a computer equipment room must be connected to a REPO circuit.

NOTE:

Wire the connector block using stranded, nonshielded wire (AWG #22 - #18, or

equivalent).

HP recommends using different colors for the positive and negative wires.
To avoid inadvertant EPO:

Minimize wire strain while connecting the REPO port.

Avoid allowing the wires to hang in the rear of the UPS.

Use tie wraps and tie wrap blocks to secure the wires tightly to the rack and the rear of the UPS.

For more information about the REPO port, see "REPO port (on page

10

)" .

For information about verifying the REPO connection, see "Verifying the REPO port connection (on page

71

)"

.

Connecting to a normally-open contact

IMPORTANT:

The remote switch must be in the open position to enable power to the UPS output.

You can install an optional REPO circuit that shuts down the entire parallel system using a single switch. To

install a REPO switch for a parallel system, the selected REPO command (NO or NC) contacts from each UPS
in the system must be in parallel.
To install a REPO switch for a parallel system:

1.

Verify that the UPS system is powered down and all power sources are removed. For more information,
see "Powering down the parallel system (on page

73

)."

2.

Mount the remote REPO switch. HP recommends mounting the REPO switch near the operator's
consoles or near the exit doors. For enclosure dimensions and wiring knockouts, see the REPO switch

manufacturer's installation instructions.