Check parallel board condition, Configuration error and ups does not start, Phase rotation verification – HP Parallel Uninterruptible Power System User Manual

Page 97

Advertising
background image

Troubleshooting 97

1.

Verify the bypass utility.

2.

Check for one of the following alarms:

o

Bypass over or under voltage

o

Bypass over or under frequency

o

Bypass unavailable

Check Parallel Board condition

Possible cause: The UPS does not recognize another paralleled UPS.
Action:

1.

From the UPS Status menu, select the Units on Parallel Card option and be sure that all UPSs appear in
the list.

2.

If any UPS is missing, verify the Parallel UPS Card connections and recheck the status from the UPS front
panel. See "Configuring the Parallel UPS Card (on page

41

)."

3.

If all UPSs appear in the list, verify the redundant signal wiring (on page

78

) connections.

4.

Set the system to Auto-Bypass mode (on page

66

).

5.

If the condition persists, contact an HP authorized service representative.

Configuration error and UPS does not start

Possible cause: The UPS failed to identify itself as a paralleled UPS within two minutes after utility power

was applied.
Action:

1.

Verify the Parallel UPS Card wiring connections. See "Configuring the Parallel UPS Card (on page

41

)."

2.

If the condition persists, contact an HP authorized service representative.

Phase rotation verification

Action: Before installing the UPS, an electrician must check the phase rotation. The rotation should be A, B,

C, or X, Y, Z.

Power is not available at the UPS output receptacle

Possible cause:

The UPS is in Standby mode (on page

64

).

the REPO switch is active or the REPO connector is missing.

Action:

1.

Reset the REPO switch

2.

Verify the REPO port connection ("

Verifying the REPO port connection

" on page

71

).

3.

For 12kVA models, be sure that the output circuit breaker is in the On position.