AMETEK 2110 Shut Height Monitor User Manual

Page 36

Advertising
background image

Installation and Programming Manual

32

Chapter 4: Programming

33

Installation and Programming Manual

Chapter 4: Programming

1. Select the function key.

The monitor displays “F-----”.

2. Select function number 302 . Select the enter key.

The monitor displays the current shut height position.

3. Enter the new position offset value. Select the enter key.

Position Offset (302)

NOTE: Make sure the unit of measurement function is selected to your desired units before

entering the value for the Position Offset function. The unit of measurement is set in
inches at the factory. For instructions on selecting the unit of measurement, see Unit of
Measurement in Section 4.3: Monitor Setup Functions.

The Position Offset function is used to synchronize the monitors displayed value with actual
shut height. This value can range from -99.999 to 999.999 inches. With the LDT installed on
the press and functioning properly, physically measure the shut height. Enter the measured
value in this function. To change the value of the Position Offset function, perform the
following steps:

Enter current
Shut Height
Position

Zero Pulse Time (305)

The Zero Pulse Time function is used to enter the pulse time that the monitor will recognize as
the absolute zero position on the LDT. The default for this function is 1.000 millisecond. This
value matches the Zero Pulse Time of the 951VP-1992 and should not require an adjustment.
The zero pulse time value can range from 1.000 to 99.999 milliseconds. To change the value of
the Zero Pulse Time function, perform the following steps:

1. Select the function key.

The monitor displays “F-----”.

2. Select function number 305 . Select the enter key.

The monitor displays the function’s current value.

3. Enter the new zero pulse time. Select the enter key.

305

Enter new
zero pulse
time

302

(F)

8

8

(F)

8

8

T13692 Chapter 4.indd

3/17/04, 6:50 AM

32