Chapter 4: Programming

35

Installation and Programming Manual

Chapter 4: Programming

Decimal Location (13)

The Decimal Location function is used to program the resolution of the shut height and all
position data shown on the monitor’s LED display. Resolution can be either displayed in whole
units, tenths, hundredths, or thousandths. Resolution choices correspond to the following values:
0 = whole unit; 1 = tenths; 2 = hundredths; and 3 = thousandths. To change the resolution
shown on the monitor’s LED display, perform the following steps:

1. Select the function key.

The monitor displays “F-----”

2. Select function number 13. Select the enter key.

The monitor displays the function’s current value.

3. Enter either a 0, 1, 2, or 3. Select the enter key.

Position Hold (15)

The Position Hold function stops the monitor from displaying irrelevant fluctuations during a
press’s stamping cycle. When the monitor’s auxiliary input is activated, this function will hold
the last position read. Either a 0, 1, or 2 can be programmed in this function. Entering a 1 will
cause the monitor to hold the last position read when power is applied to the auxiliary input.
Entering a 2 will cause the monitor to hold the last position read when power is taken away
from the auxiliary input. Entering a 0 disables this function. The default for this function is 0.
Enabling this function disables the Move Detection Time-Out function. When the Position Hold
function is enabled, the value for the Move Detection Time-Out is then used for the Position
Hold dwell time. The position hold dwell time is the amount of time the monitor continues to
hold the shut height position after the auxiliary input is released (or activated, depending on
the input’s programmed state). To enable or disable the Position Hold function, perform the
following steps:

1. Select the function key.

The monitor displays “F-----”

2. Enter function number 15. Select the enter key.

The monitor displays the function’s current value.

3. Enter either 0, 1, or 2. Select the enter key.

NOTE: The default time for the position hold dwell may be too long for your application. To

change this value for your application, perform the following steps.

15

Enter either
0, 1, 2, or 3

13

Enter either
0, 1, or 2