Installation and Programming Manual

44

Chapter 4: Programming

45

Installation and Programming Manual

Chapter 4: Programming

3. Enter function number X02. Select enter key.


The monitor displays current minimum position value.

4. Enter 500. Select enter key. This sets minimum position value at 500 counts.
The monitor displays 000500.

5. Select function key.

The monitor displays “F----”.

6. Enter function number X05. Select enter key.

The monitor displays current voltage output value linked to minimum

position value.

7. Enter 2. Select enter key. This sets a minimum voltage output value of

2VDC for 500 counts or less.

The monitor displays 002000.

C) Scaling Analog Output

The analog output is scaled by programming a minimum position value followed by the

analog output value required at that position. A maximum position value is then

programmed followed by the analog output required at that position.

The analog output value specified can be any value within the following allowable

range:

Voltage

-10 VDC to 10 VDC

Current

0mA to 20mA

The analog output will stop changing upon reaching the minimum and maximum values

programmed. This allows selection of a nonstandard output like 2 to 8 VDC or 10 to 20

mA.

The position range over which the analog output develops can be any portion of the total

change seen by the Interface Module.

Example: Program analog output channel 1 for 2 to 8 VDC over 500 to 2000 count

change.

1. Select Voltage output as described earlier under step A

2. Select function key.

The monitor displays “F----”.

8

(F)

8

8

8

X02

Enter
000500

X05

Enter
002000

(F)