No response from datalogger through sc32b or modem, Peripheral – Campbell Scientific UT10 10 foot Tower w/ Grounding Kit and Hinged Base User Manual

Page 62

Advertising
background image

UT10 Weather Station

D. Disconnect any communications or storage peripherals from the

datalogger.

E. Reset the datalogger by turning the power switch to “OFF”, then to “ON”

or disconnecting and reconnecting the battery.

F. If still no response, call Campbell Scientific.

9.2.2 No Response from Datalogger through SC32B or Modem Peripheral

At the datalogger:

A. Make sure the battery has been installed, and the power switch, if any, is

“ON”.

B. Use a voltmeter to measure the voltage on the 12 V and G terminals; the

voltage must be between 9.6 and 16 Vdc.

C. Make sure the datalogger is connected to the modem, and the modem is

properly configured and cabled (Section 8.3, Communication and Data

Storage Peripherals).

At the computer:

D. Make sure the Station File is configured correctly (LoggerNet or PC400

Manual).

E. Check the cable(s) between the serial port and the modem. If cables have

not been purchased through Campbell Scientific, check for the following

configuration using an ohm meter:

25-pin serial port:
computer end modem end
2

2

3

3

7

7

20

20

9-pin serial port:
computer end modem end
2

3

3

2

4

20

5

7

F. Make sure the modem is properly configured and cabled (Section 8.3,

Communication and Data Storage Peripherals).

G. If still no response, call Campbell Scientific.