Shut down the pump, Make the final alignment of the pump and driver, Dowel the pump casing (optional) – Goulds Pumps 3700 - IOM User Manual

Page 56

Advertising
background image

Commissioning, Startup, Operation, and Shutdown

CAUTION:

• Avoid excessive vibration levels. Excessive vibration levels can damage the bearings, stuffing box

or seal chamber, and the mechanical seal, which can result in decreased performance.

• Avoid increased radial load. Failure to do so can cause stress on the shaft and bearings.
• Avoid heat build-up. Failure to do so can cause rotating parts to score or seize.
• Avoid cavitation. Failure to do so can cause damage to the internal surfaces of the pump.

Operation under freezing conditions

NOTICE:
Do not expose an idle pump to freezing conditions. Drain all liquid that is inside the pump and
the cooling coils. Failure to do so can cause liquid to freeze and damage the pump.

Shut down the pump

WARNING:
The pump can handle hazardous and toxic fluids. Identify the contents of the pump and observe proper
decontamination procedures in order to eliminate the possible exposure to any hazardous or toxic fluids.
Wear the proper personal protective equipment. Potential hazards include, but are not limited to, high
temperature, flammable, acidic, caustic, explosive, and other risks. You must handle and dispose of
pumped fluid in compliance with the applicable environmental regulations.

1. Slowly close the discharge valve.
2. Shut down and lock the driver to prevent accidental rotation.

Make the final alignment of the pump and driver

WARNING:

• Always disconnect and lock out power to the driver before you perform any installation or

maintenance tasks. Failure to disconnect and lock out driver power will result in serious physical
injury.

• Follow shaft alignment procedures in order to prevent catastrophic failure of drive components or

unintended contact of rotating parts. Follow the coupling installation and operation procedures from
the coupling manufacturer.

You must check the final alignment after the pump and driver are at operating temperature. For
initial alignment instructions, see the Installation chapter.
1. Run the unit under actual operating conditions for enough time to bring the pump, driver,

and associated system to operating temperature.

2. Shut down the pump and the driver.
3. Remove the coupling guard.

See Remove the coupling guard in the Maintenance chapter.

4. Check the alignment while the unit is still hot.

See Pump-to-driver alignment in the Installation chapter.

5. Reinstall the coupling guard.
6. Restart the pump and driver.

Dowel the pump casing (optional)

You will need the following tools:

• Two number 7 taper pins

• One number 7 taper pin reamer

• 0.3320 in. or "Q" size drill

54

Model 3700, API Type OH2 / ISO 13709 1st and 2nd Ed. / API 610 8/9/10/11th Ed. Installation, Operation, and Maintenance

Manual

Advertising