MAINTENANCE & INSTRUCTION BOOKLET

6 S

INGLE STATION SUB

-

BASE

6.1 G

ENERAL INFORMATION

VS18/VS26 offers single station sub-bases for valves located remotely from valve island.

Below listed connectors are available for the electrical connection to the VS18/VS26 single
station sub-base. Please refer to the indicated section for detailed information on these.
• M12 connector

Section

6.2

• NPTF1/2” conduit entry with flying leads

Section

6.3


Please see information on assembly of valve and sandwich plates in section

5.1.4

.


6.1.1 24V DC power supply

VS18/VS26 single station sub-base 24V DC versions are designed to be used with a protective
extra low voltage (PELV) power supply (UL Class 2 Supply only). Therefore, the power supply
used must meet the IEC standard 742/EN60742/VDE 0551 (PELV).

6.1.2 115V AC power supply

VS18/VS26 single station sub-base 115V AC versions correspond to the protection class I.
Connection of the protective earth (PE) ground is required.

6.1.3 Max current load on valve connectors with 24V DC

I

max

= 60mA * n

n = number of energized solenoids

6.1.4 Max current load on valve connectors with 115V AC

I

max

= 13mA * n

n = number of energized solenoids

VS2672926-KG00E_05/07 Page

34/97