Profibus dp, Profibus dp pin assignment, Rofibus – Norgren VS18 Series Valve Advantage User Manual

Page 52

Advertising
background image

VS18/VS26

MAINTENANCE & INSTRUCTION BOOKLET

8.2 P

ROFIBUS

DP

Norgren Profibus DP Fieldbus systems conform to
DIN 19245 part 3.

Communication system:

2-wire RS485 hardware
communication protocol

Baud rate:

9.6 kBit/s to 12 MBit/s. Automatic detection.

Maximum nodes per network:

126

total number of I/O per network:

32256

Bus topology:

Line


8.2.1 Profibus DP pin assignment

2 x M12 5-pin version (B-coded / IP65)

Male

Female

Pin no.

Function

1 5VI

isolated

2

Line A (green)

3 0VI

isolated

4

Line B (red)

Communication in

Communication out

Looking into node connectors

5 Shield
Threaded
joint

Shield





1 x D-Sub 9-pin version (IP40)

Female

Pin no.

Function

1 Shield
2 N/C
3

Line B (red) RxD / TxD-P

4 N/C
5

DGND (0VI) isolated

6

VP (5VI) isolated

7 N/C
8

Line A (green) Rxd / TxD-N

9 N/C

Looking into node connectors