Diagnostics, Devicenet led indicators – Norgren VS18 Series Valve Advantage User Manual

Page 62

Advertising
background image

VS18/VS26

MAINTENANCE & INSTRUCTION BOOKLET

8.3.5 Diagnostics

The VS18/VS26 DeviceNet slave has diagnostic attributes to inform a master of its current
state. With these attributes it is possible to monitor the state of the +24V valve power. This can
be achieved by using the DeviceNet message: DeviceNet Class Number 3, Instance 1, Attribute
Number 0x69, which can be explicitly requested. This message will return 1 byte of data, with
value 0x01 indicating that the valve power is present or 0x00 indicating that the valve power is
not present.

8.3.6 DeviceNet LED indicators

VB (green)

This LED will only be energised when 24 volts is applied to the electronics
power terminal of the power supply connector.


5V (green)

This LED will only be energised when the Network power is connected to the
Network connector, indicating that the logic circuit of the module is powered.


MS (red/green)–

This LED indicates the device and whether it is operational or working
correctly.


NS (red/green)–

This LED indicates the status of the CAN communication link.


VA (green)

This LED will only be energised when 24 volts is applied to the valve power
terminal of the power supply connector.


Indicator status during powering up and commissioning

Condition

VB

5V

MS

NS

VA

Power up

on

on

single flash

single flash
green/red

on

Autom. baud rate detection active

on

on

green

off

on

Changing address during
commissioning

on on green

green

on

Device in a pre-operation state

on

on

green

flashing green

on

Device in an operation state

on

on

green

green

on

Connection time out

on

on

green

flashing green

on

Failed communication

on

on

green

red

on

Un-recoverable fault

on

on

red

dependant

on


VS2672926-KG00E_05/07 Page

62/97

Advertising
This manual is related to the following products: