Interbus-s led indicators – Norgren VS18 Series Valve Advantage User Manual

Page 73

Advertising
background image

VS18/VS26

MAINTENANCE & INSTRUCTION BOOKLET

8.5.6 Interbus-S LED indicators

VB (green) –

This LED will only be energised when 24 volts is applied to the electronics
power terminal of the power supply connector.


UL (green) –

This LED will only be energised when the Network power is connected to the
Network connector, indicating that the logic circuit of the module is powered.


RC (green) –

This LED will only be energised when a cable connection is made to the
incoming connector of the device.


BA (green) –

This LED will only be energised when communication is established on the
network from the master.


RD (yellow) –

This LED will only be energised when no connection is made to the device, or
the master is in an offline state.


VA (green) –

This LED will only be energised when 24 volts is applied to the valve power
terminal of the power supply connector.


Indicator status during powering up and commissioning

Condition

VB

UL

RC

BA

RD

VA

Power

up

on on off off on on

No operation state (master offline)

on

on

on

off

on

on

Establishing communication with
master

on on flickering

on off on

Device in an operation state

on

on

on

on

off

on

VS2672926-KG00E_05/07 Page

73/97

Advertising