8.4.3 CANopen address and baud rate setting

The VS18/VS26 CANopen valve island address can be set within the range 0 to 99 (rotary
switch) resp. 127 (software). To set the address, use the selector switches accessible by
removing the securing screw and lifting the hinged cover of the address switches. The two
rotary switches allow an address range of 1 to 99. The valve island needs a power reset to
accept a new address. When position 0 is selected on both switches the address may be set
through software via a capable master.
Default address = 127



Changing the address of the node via software:

Using a CANopen configuration tool connected to the network, the address of each node maybe
changed by the following method:

Send an SDO Telegram command to the node at SDO index 2100h containing the new node
address, valid range 1-127. View example of SDO message below

Description

SDO Index

Sub Index

Value

EEPROM node address

2100h

0

1 – 127


The Norgren CANopen node also supports the layer setting service (LSS). The following
configuration services are available

Service

COB-ID Byte 0 Byte 1

Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7

Switch Mode Global 2021h

CS=04 Mode

Reserved

Configure Node ID

2021h

CS=17 Address Reserved

Configure Bit Timing 2021h

CS=19 Table

Selector

Table
Index

Reserved

Activate Bit Timing

2021h

CS=21 Switch Delay

Reserved

Store Configuration 2021h

CS=23 Reserved


Following are VS18/VS26 CANopen baud rates, which are detected automatically:
10 kBit/s

20 kBit/s

50 kBit/s

125 kBit/s

250 kBit/s

500 kBit/s

800 kBit/s

1'000 kBit/s


VS2672926-KG00E_05/07 Page

67/97