Drive line and flange bolts – Hale SMR User Manual

Page 59

Advertising
background image

Stainless Max Series Pumps

4-7

Preventive Maintenance

4. Compare the readings of the test gauge and the apparatus

gauge. Note any difference.

5. Stop the priming pump and observe the gauge.

If the vacuum falls more than 10 inches of Hg in 5 minutes, it is
an indication of at least one air leak.

Vacuum leaks may often be detected audibly if the apparatus
engine is turned off. Correct leaks immediately to return the
pump to service.

6. Test the suction hose as follows:

a. Attach the suction hose to the pump.
b. Place a suction tube cap on the end of the hose in place of a

strainer.

c. Close all valves and drains. Cap all suction openings and the

outlet of the suction side relief valve (if so equipped).

d. Connect a calibrated vacuum gauge or manometer to the

intake test gauge connection on the pump panel.

e. Engage the priming pump until the gauge indicates at least

22 IN-hg vacuum.

f. Watch the gauge. If the vacuum falls more than 10 inches in 5

minutes, it is an indication of at least one air leak.

g. Verify that the test gauge and the apparatus gauge display the

same readings.

h. Repair or replace any gauges that do not display the correct

pressure.

IMPORTANT!

IF LEAKS CANNOT BE DETECTED BY FOLLOWING THE PROCEDURE, IT
IS ADVISABLE TO TEST THE PUMP HYDROSTATICALLY. TO TEST:

OPEN ALL THE VALVES

PLACE CAPS ON ALL VALVES

CONNECT A POSITIVE PRESSURE SOURCE

INSPECT THE PUMP FOR LEAKS

Drive Line and Flange Bolts

Check all drive line and flange bolts to ensure:

1. No bolts are missing.