Standard Telegrams (concluded)

Standard

telegram

Master

Slave

Bytes

Meaning

204

S

⇒ M

0…7

8

9…12

13

14…15

Parameter Channel
Exception Status
Process Value float
OneOfN Status Extension
Trip Relay 1-2

205

1)

S

⇒ M

1

2

Status (Bit 4…7)

2)

and

Measurement Value

2)

Measurement Value

2)

206

1)

M

⇒ S

1…2

Two bytes are sent to the slave but are not
processed by the slave

1)

Available in TTR compatibility mode only.

2)

Bit 7: 0 = no error / 1 = error

Bit 6: 0 = Trip Point 1 not activated / 1 = Trip Point 1 activated
Bit 5: 0
Bit 4: 0

The measurement value is given as a 12-bit value. Byte 1 / Bit 3 represents the MSB,
Byte 2 / Bit 0 the LSB

p [mbar] = 10

Measurement_Value / 482 - 4.778

p [Torr] = 10

Measurement_Value / 482 - 4.9029

p [Pa] = 10

Measurement_Value / 482 - 2.778

The devices support the following standard telegrams:

Standard

telegram

M

⇒ S

Standard

telegram

S

⇒ M

Configuration data

- 1

0x42,0x82,0x05,0x03

- 2

0x42,0x84,0x05,0x08

- 3

0x44,0x84,0x05,0x05, 0x05, 0x03

- 4

0x44,0x86,0x05,0x05, 0x05, 0x08

2 7

0xC4,0x87,0x8A,0x0A,0x0A,0x05,0x03

2 8

0xC4,0x87,0x8C,0x0A,0x0A,0x05,0x08

2 9

0xC6,0x87,0x8C,0x0A,0x0A,0x05,0x05, 0x05, 0x03

2 10

0xC6,0x87,0x8E,0x0A,0x0A,0x05,0x05, 0x05, 0x08

- 201

0x44,0x85,0x05,0x03,0x05,0x0A

- 202

0x44,0x87,0x05,0x08,0x05,0x0A

2 203

0xC6,0x87,0x8D,0x0A,0x0A,0x05,0x03,0x05,0x0A

2 204

0xC6,0x87,0x8F,0x0A,0x0A,0x05,0x08,0x05,0x0A

206 205

0xA1,0x91


4.4.2 Configuration Data