Safety instructions, Warnings – Lenze E94APNExxx4 User Manual

Page 41

Advertising
background image

Safety instructions

Safety instructions for the installation according to UL or UR

2

l

41

EDK94PNE245 DE/EN/FR/ES/IT 2.0

2.4

Safety instructions for the installation according to U

L

or U

R

J

Warnings!

ƒ

Maximum surrounding air temperature: 55 °C.

ƒ

For use in a pollution degree 2 environment.

ƒ

Branch circuit protection:
Suitable for use on a circuit capable of delivering not more than 18000 rms
symetrical amperes, 500 V max., when protected by H or K5 fuses.

ƒ

Voltage of the fuses must at least be suitable with the input voltage of the
drive.

ƒ

E94APNE1004: Use 60/75 °C copper wire only, except for control circuits.

ƒ

E94APNE2454: Use 75 °C copper wire only, except for control circuits.

Branch circuit protection

Type

Fuse [A]

E94APNE1004

100

E94APNE2454

250