Technical data

General data and operating conditions

3

l

43

EDK94PNE245 DE/EN/FR/ES/IT 2.0

Connection conditions for DC power supply module

AC mains operation

Direct connection

DC−bus operation

Direct connection of axis modules via terminals or busbar
system
More information can be found in the Hardware Manual,
chapter "DC−bus operation".

Environmental conditions

Climate

Storage

IEC/EN 60721−3−1

1K3 (−25 ... +60 °C)

Transport

IEC/EN 60721−3−2

2K3 (−25 ... +70 °C)

Operation

IEC/EN 60721−3−3

3K3 (−10 ... +55 °C)
Current derating at +45 ... +55 °C: 2.5 %/°C

Site altitude

0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of 5 %/1000 m

Pollution

EN 61800−5−1

Pollution degree 2

Vibration resistance

(9.81 m/s

2

= 1 g)

Transport

IEC/EN 60721−3−2

2M2

EN 61800−2

2 ... 9 Hz: amplitude 3.5 mm

10 ... 200 Hz: acceleration resistant up to 10 m/s

2

200 ... 500 Hz: acceleration resistant up to 15 m/s

2

Operation

Germanischer Lloyd

5 ... 13.2 Hz: amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g

IEC/EN 60068−2−6

10 ... 57 Hz: amplitude 0.075 mm

57 ... 150 Hz: acceleration resistant up to 10 m/s

2