Consignes de sécurité
Consignes de sécurité pour l’installation selon UL ou UR
l
69
EDK94PNE245 DE/EN/FR/ES/IT 2.0
2.4
Consignes de sécurité pour l’installation selon U
L
ou U
R
J
Warnings !
ƒ
Maximum surrounding air temperature: 55 °C.
ƒ
For use in a pollution degree 2 environment.
ƒ
Branch circuit protection:
Suitable for use on a circuit capable of delivering not more than 18000 rms
symetrical amperes, 500 V max., when protected by H or K5 fuses.
ƒ
Voltage of the fuses must at least be suitable with the input voltage of the
drive.
ƒ
E94APNE1004: Use 60/75 °C copper wire only, except for control circuits.
ƒ
E94APNE2454: Use 75 °C copper wire only, except for control circuits.
Branch circuit protection
Type
Fuse [A]
E94APNE1004
100
E94APNE2454
250