Wiring the device

5.1

Important notes

{

Danger!

Dangerous voltage
All power terminals remain live for at least three minutes after mains
disconnection.
Possible consequences:

ƒ

Death or severe injuries when touching the power terminals.

Protective measures:

ƒ

Wait for at least three minutes before working on the power terminals.

ƒ

Check that all power terminals are deenergised.

{

Danger!

Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:

ƒ

Death or severe injuries when the device is touched in the event of a fault.

Protective measures:

ƒ

Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor diameter

³ 10 mm

2

or PE conductor must be connected twice)

(

Stop!

No device protection in the event of too high mains voltages
The mains input is not fused internally.
Possible consequences:

ƒ

Destruction of the device if the mains voltage is too high.

Protective measures:

ƒ

Observe the max. permissible mains voltage.

ƒ

Fuse the device correctly on the supply side against mains fluctuations and
voltage peaks.