Final works

6

l

58

EDK94PNE245 DE/EN/FR/ES/IT 2.0

6

Final works

{

Danger!

Dangerous voltage!
When the mains voltage is switched off, the DC bus is still charged for at least
about 3 minutes.

ƒ

The state of charge is not indicated!

ƒ

On synchronous motors self−discharge only starts after a possible feedback
operation has been completed.

ƒ

Discharging the DC bus in a controlled manner via the brake chopper/brake
resistor requires the external 24 V supply (

^ digital input DI1).

Possible consequences:

ƒ

Death or severe injuries when touching the terminals.

Protective measures:

ƒ

Before starting work on the system check that it is deenergised.

ƒ

Wait at least 3 minutes after switching off the mains voltage.

ƒ

Only remove deenergised devices from the installation backplanes and do
not touch any terminals.

How to proceed:

ƒ

Adjust the setting for the mains voltage/brake chopper threshold to the mains

Setting of mains voltage/brake chopper threshold

2

Pos.

3

U

LN

[V]

U

BRmax

[V]

1

500 V
480 V
400 V
230 V

ON

MAINS

12

500

790

OFF
OFF

480

765

ON

OFF

400

725

OFF

ON

230

390

ON
ON

94APNEDS01

ƒ

Switch on the 24 V supply

ƒ

Check the operating status by means of the LED display

If you want to continue commissioning:

ƒ

Switch on the mains