4 wiring of control connections, Wiring of control connections, Wiring the device – Lenze E94APNExxx4 User Manual
Page 57
![background image](/manuals/565778/57/background.png)
Wiring the device
Wiring
Wiring of control connections
l
57
EDK94PNE245 DE/EN/FR/ES/IT 2.0
5.3.4
Wiring of control connections
24 V supply
Terminal X11
Labelling
Description
GE
GND external supply
24E
24 V external supply through safely separated power supply unit
(SELV/PELV)
IEC 61131−2, 19.2 ... 28.8 V, residual ripple max. ±5 %
Current during operation: 1.4 A
Starting current: 4 A for 100 ms
9400SSP000X2
SB
Reserved
Terminal data
Conductor cross−section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb−in]
Flexible
0.2 ... 2.5
24 ... 12
Spring terminal
With wire end
ferrule
Stripping length / contact length: 10 mm
Digital inputs, digital outputs
Terminal X12
Labelling
Description
GOI
GND digital out / in
DI1
Activation of brake chopper
(external 24 V supply required)
DO1
Mains OK
DO2
Brake chopper active
DO3
Short circuit in brake chopper
SSP9400X12
DO4
Heatsink overtemperature
Terminal data
Conductor cross−section
Tightening torque
[mm
2
]
[AWG]
[Nm]
[lb−in]
Flexible
0.2 ... 2.5
24 ... 12
Spring terminal
With wire end
ferrule
Stripping length / contact length: 10 mm