Mounting the device

Arrangement of the devices

4

l

48

EDK94PNE245 DE/EN/FR/ES/IT 2.0

4.2

Arrangement of the devices

L1

L2

L3

M

3~

M

3~

M

3~

M

3~

E94AZxPxxxx

E94AZxPxxxx

E94APNExxxx

E94AZEX100

E94AZPxxxxx

E94AZPxxxxx

E94AZPxxxxx

E94AZPxxxxx

...

...

+UG

-UG

+UG

-UG

+UG

-UG

0

1

+

(E94AZPPxxxx)

SSP94FF003

Fig.4−1

Arrangement concept
0

Standard mounting: side mounting

1

Mounting variant: top mounting

E94AZxPxxxx

Filter

E94APNExxxx

9400 DC power supply module
(up to 36 A/18 kW with E94AZPPxxxx installation backplane)

E94AZEX100

DC input module

E94AZPxxxxx

Installation backplane for 9400 axis module

The technical data must be taken into account when planning and dimensioning a DC−bus
interconnection.

Arrange the devices as follows for operation in DC−bus interconnection via the DC busbars:

ƒ

Mount the devices side by side from the left to the right.

ƒ

Install the supplying device on the left side:
– DC power supply module (in a first row),
– DC feeding point (in following rows).

ƒ

Install the Multi Drive axis controllers from left to right with decreasing powers.

ƒ

Single Drive axis controllers can be integrated to increase the braking power. These
axis controllers must be equipped with the optional busbar set (E94AZJAxxx).

Protective measures for the cables leading to an E94AZEX100 input module must be
dimensioned for a rated current of 100 A. If smaller cable cross−sections are used, the
fusing has to be adapted according to the applicable standards or technical rules. More
information can be found in the chapter "DC−bus operation" of the Hardware Manual.