4 heat sinking, 5 line (mains) fusing, 6 fuse recommendations – Lenze S94P01B2 User Manual

Page 16: Installation

Advertising
background image

S94P01B2

14

Installation

NOTE

The ground connection from the filter must be wired to solid earth
ground, not machine ground.

If the end-user is using a CE-approved motor, the AC filter combined with the
recommended motor and encoder cables, is all that is necessary to meet the EMC
directives listed herein. The end user must use the compatible filter to comply with CE
specifications. The OEM may choose to provide alternative filtering that encompasses
the PositionServo 940 drive and other electronics within the same panel. The OEM has
this liberty because CE requirements are for the total system.

3.4

Heat Sinking

The PositionServo 940 drive contains sufficient heat sinking within the specified ambient
operating temperature in their basic configuration. There is no need for additional heat
sinking. However, you must ensure that there is sufficient clearance for proper air
circulation. As a minimum, you must allow an air gap of 25 mm above and below the
drive.

3.5

Line (Mains) Fusing

External line fuses must be installed on all PositionServo drives. Connect the external
line fuse in series with the AC line voltage input. Use fast-acting fuses rated for 250
VAC or 600 VAC (depending on model), and approximately 200% of the maximum
RMS phase current.

3.6

Fuse Recommendations

Type

(1)

AC Line

Input Fuse

(1ш/3ш)

Miniature

Circuit Breaker

(1)

(1ш/3ш)

AC Line

Input Fuse or

Breaker

(2)

(3)

(N. America)

DC Bus Input

Fuse

(4)

Amp Ratings

E94P020S1N

M20/M10

C20/C10

20/10

10

E94P040S1N

M32/M20

C32/C20

30/20

20

E94P020S2F

M20

C20

20

15

E94P040S2F

M20

C20

20

20

E94P080S2F

M32

C32

32

40

E94P100S2F

M40

C40

40

45

E94P020Y2N

M20/M16

C20/C16

20/15

15

E94P040Y2N

M20/M16

C20/C16

20/15

20

E94P080Y2N

M32/M20

C32/C20

30/20

40

E94P100Y2N

M40/M25

C40/C25

40/25

45

E94P120Y2N

M50/M32

C50/C32

50/30

55

E94P020T4N

M10

C10

10

10

E94P040T4N

M10

C10

10

20

E94P050T4N

M16

C16

15

25

E94P060T4N

M20

C20

20

30

(1)

Installations with high fault current due to large supply mains may require a type D circuit breaker.

(2)

UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN, JJS or equivalent.

(3)

Thermal-magnetic type breakers preferred.

(4)

DC-rated fuses, rated for the applied voltage. Examples Bussman KTM or JJN as appropriate.