Interface – Lenze S94P01B2 User Manual

Page 35

Advertising
background image

S94P01B2

33

Interface

Halls Order

Each hall signal is in phase with one of the three phase-phase voltages from the motor
windings. Hall order number defines which hall sensor matches which phase-phase
voltage. Motor phases are usually called R-S-T or U-V-W or A-B-C. Phase-Phase
voltages are called Vrs, Vst, Vtr. Halls are usually called HALL-A, HALL-B, HALL-C or
just Halls 1, 2, 3. A motor’s phase diagram is supplied by motor vendor and usually can
be found in the motor data sheet or by making a request to the motor manufacturer. A
sample phase diagram is shown below.

S912

The Halls Order is obtained as follows:

1. By looking at the “Vrs” Output Voltage, determine which Hall Voltage is lined

up with (or in phase with) this voltage. We can determine which Hall Voltage
is in phase with the Vrs Output Voltage by drawing vertical lines at those
points where it crosses the horizontal line (zero). The dashed lines at the
zero crossings (above) indicate that Hall B output is lined up with (and in
phase with) the Vrs Output Voltage.

2. Look at the “Vst” Output Voltage. Determine which Hall Voltage is in phase

with this Voltage. As can be seen, Hall C output is in phase with the Vst
Output Voltage.

3. Look at the “Vtr” Output Voltage. Determine which Hall Voltage is in phase

with this Voltage. As can be seen, Hall A output is in phase with the Vtr
Output Voltage.

NOTE

If hall sensors are in phase with the corresponding phase voltage
but are inverted 180 degrees (hall sensor waveform edge aligns with
the phase-phase voltage waveform but the positive hall sensor cycle
matches the negative phase-phase waveform or visa-versa), you must
check the “Inverted” check box.