4 p4 - motor feedback / second loop encoder input, Interface – Lenze S94P01B2 User Manual

Page 19

Advertising
background image

S94P01B2

17

Interface

Pin

Name

Function

10

BB-

Buffered Encoder Output: Channel B-

(1)

11

BZ+

Buffered Encoder Output: Channel Z+

(1)

12

BZ-

Buffered Encoder Output: Channel Z-

(1)

13-19

Empty

20

AIN2+

Positive (+) of Analog signal input

21

AIN2-

Negative (-) of Analog signal input

22

ACOM

Analog common

23

AO

Analog output

24

AIN1+

Positive (+) of Analog signal input

25

AIN1 -

Negative (-) of Analog signal input

26

IN_A_COM

Digital input group ACOM terminal

(3)

27

IN_A1

Digital input A1

28

IN_A2

Digital input A2

29

IN_A3

Digital input A3

(3)

30

IN_A4

Digital input A4

31

IN_B_COM

Digital input group BCOM terminal

32

IN_B1

Digital input B1

33

IN_B2

Digital input B2

34

IN_B3

Digital input B3

35

IN_B4

Digital input B4

36

IN_C_COM

Digital input group CCOM terminal

37

IN_C1

Digital input C1

38

IN_C2

Digital input C2

39

IN_C3

Digital input C3

40

IN_C4

Digital input C4

41

RDY+

Ready output Collector

42

RDY-

Ready output Emitter

43

OUT1-C

Programmable output #1 Collector

44

OUT1-E

Programmable output #1 Emitter

45

OUT2-C

Programmable output #2 Collector

46

OUT2-E

Programmable output #2 Emitter

47

OUT3-C

Programmable output #3 Collector

48

OUT3-E

Programmable output #3 Emitter

49

OUT4-C

Programmable output #4 Collector

50

OUT4-E

Programmable output #4 Emitter

(1)

See Note 1, Section 4.1.7 - Connector and Wiring Notes

(2)

See Note 2, Section 4.1.7 - Connector and Wiring Notes

3)

See Note 3, Section 4.1.7 - Connector and Wiring Notes

4.1.4 P4 - Motor Feedback / Second Loop Encoder Input

P4 is a 15-pin DB connector that contains connections for Hall Effect sensors and
incremental encoder feedback. Refer to the P4 pin assignments table for the connector
pin assignments. Encoder inputs on P4 have 26LS32 or compatible differential receivers
for increased noise immunity. Inputs have all necessary filtering and line balancing
components so no external noise suppression networks are needed.

All conductors must be enclosed in one shield and jacket around them. Lenze
recommends that each and every pair (for example, EA+ and EA-) be twisted. In order
to satisfy CE requirements, use of an OEM cable is recommended. Contact your Lenze
representative for assistance.

Advertising