S94P01B2

51

Operation

Gain Scaling set OK

Motor Velocity resembles Commanded

Velocity. Motor Velocity is reasonably close

with a slight overshoot.

Gain Scaling set too HIGH

Motor Velocity shows significant overshoot

following the acceleration periods.

Gain Scaling set significantly too HIGH

Motor Velocity exhibits instability throughout

the steady state Commanded Velocity.

Depending on the system begin tuned, the motor may go from stable operation (little to
no overshoot with stable steady state velocity) to instability (continuous and pronounced
oscillations during steady state command) very quickly as gains scaling is increased.
The bandwidth for allowing some overshoot with a quick settle time may be very small
and may only be achieved through adjustment of the Velocity P-Gain, as described in
Step 2. Set the gain scaling parameter to the value preceding that where significant
overshoot or continuous instability occurs. With the Gain scaling parameter set move
onto tuning the velocity P and I gains.