2 technical data, 1 general data/operating conditions, Technical data – Lenze ECSDKxxx User Manual

Page 45: General data/operating conditions, 2technical data

Advertising
background image

Technical data

General data/operating conditions

2

l

45

EDKCSDK002 DE/EN/FR 1.1

2

Technical data

2.1

General data/operating conditions

Standards and operating conditions

Conformity

CE

Low−Voltage Directive (73/23/EWG)

Approvals

UL 508C

Power Conversion Equipment
Underwriter Laboratories (file no. E132659)
for USA and Canada

Vibration resistance

Accelerational stability up to 0.7 g (Germanischer Lloyd, general
conditions)

Climatic conditions

Class 3K3 to EN 50178 (without condensation, relative humidity
30 ... 95 %)

Degree of pollution

VDE 0110 part 2 pollution degree 2

Packaging (DIN 4180)

Delivery packing

Permissible
temperature range

Transport

−25 ... +70 °C

Storage

−25 ... +55 °C

Operation

0 ... +55 °C

reduce the rated AC current by 2 %/°C above +40°C

Permissible installation height

0 ... 4000 m amsl

reduce rated AC current by 5%/1000 m above 1000 m
amsl

Installation

Installation into control cabinet

Mounting position

Vertically suspended

Free space

Above

³ 65 mm

Below

³ 65 mm
with shield assembly set ECSZS000B0B001: > 195 mm

To the sides

Side−by−side mounting without any clearance

Advertising