2 rated data, Rated data, Technical data – Lenze ECSDKxxx User Manual

Page 46

Advertising
background image

Technical data

Rated data

2

l

46

EDKCSDK002 DE/EN/FR 1.1

General electrical data

EMC

Compliance with EN 61800−3

Noise emission

Compliance with limit value class A to EN 55011
(achieved with application−specific collective filter)

Noise immunity

Requirements to EN 61800−3

Requirements

Standard

Severity

ESD

1)

EN 61000−4−2

3, i. e.

l

8 kV with air discharge

l

6 kV with contact
discharge

High frequency in cables

EN 61000−4−6

10 V; 0.15 ... 80 MHz

RF interference
(enclosure)

EN 61000−4−3

3, i. e. 10 V/m;
80 ... 1000 MHz

Burst

EN 61000−4−4

3/4, i. e. 2 kV/5 kHz

Surge (on mains cable)

EN 61000−4−5

3, i. e. 1.2/50

ms

l

1 kV phase−phase

l

2 kV phase PE

Insulation resistance

Overvoltage category III to VDE 0110

Discharge current against PE (to EN 50178)

> 3.5 mA AC for operation with corresponding controllers

Enclosure

l

IP20 for standard mounting

l

IP20 for mounting in cold−plate technique

l

IP20 for mounting in push−through technique; IP54 on the heatsink
side

Protective insulation of control circuits

Safe disconnection from supply: Double/reinforced insulation to
EN 50178;
Rated insulation voltage 300 V x

√2

1)

Noise immunity in the above−mentioned severities must be guaranteed through the
control cabinet! The user must check the compliance with the severities!

2.2

Rated data

,

The most important rated data are located on the nameplate of the
device. Additional data can be found in the detailed documentation.