Electrical installation
Wiring
Operation with another supplier
l
61
EDKCSDK002 DE/EN/FR 1.1
4.4.2
Operation with another supplier
(
Stop!
ƒ
After mains connection, wait at least one second before bridging
the charging current limitation (X26 = HIGH).
ƒ
Only release the controller (X6/SI1 = HIGH) if the charging current
limitation is bridged.
t [s]
HIGH (1)
LOW (0)
ECSx
: X6/SI1
ü
t [s]
100 %
0 %
t [s]
HIGH (1)
LOW (0)
ECSxK: X26 (24 V DC)
t [s]
HIGH (1)
LOW (0)
K1
U
ZK
1
ECSXK011
Fig.9−3
Level/time diagrams for operation with other supplier
ECSx
ü
Axis module of series ECS
U
ZK
DC−bus voltage
ECSxK
Capacitor module of series ECS
K1
Mains contactor