Electrical installation

Power connections

4

l

55

EDKCSDK002 DE/EN/FR 1.1

4.2

Power connections

(

Stop!

ƒ

The capacitor module is approved exclusively for operation at
symmetrical mains. An operation at external conductor−earthed
mains is not permissible.

ƒ

Observe the maximum permissible mains voltage. A higher voltage
destroys the capacitor module.

ƒ

The discharge current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
According to EN 50178, a fixed installation is required. The
PE connection must be made according to EN 50178.

ƒ

All power connections are designed as pluggable and coded. The connectors
are part of the ECSZA000X0B capacitor module accessories set. It must be
ordered separately.

ƒ

Installation of cables acc. to EN 60204−1.

ƒ

The cables used must comply with the approvals required for the respective
application (e.g. VDE, UL, etc.).

Terminal assignment

Terminal

Function

Electrical data

X23

DC−bus voltage connection

X23/+UG

Positive supply of DC−bus voltage

Application and type−dependent
0 ... 770 V
up to 24.5 A (

^

46)

X23/+UG

X23/−UG

Negative supply of DC−bus voltage

X23/−UG

X23/PE

Earth connection

X23/PE

Cable cross−sections and screw−tightening torques

Cable type

Wire end ferrule

Possible cable
cross−sections

Tightening torque

Stripping
length

Terminal strip X23

Rigid

0.2 ... 10 mm

2

(AWG 24 ... 8)

1.2 ... 1.5 Nm

(10.6 ... 13.3 lb−in)

5 mm

Flexible

Without wire end ferrule

0.2 ... 10 mm

2

(AWG 24 ... 8)

With wire end ferrule

0.25 ... 6 mm

2

(AWG 22 ... 10)

With TWIN wire end
ferrule

0.25 ... 4 mm

2

(AWG 22 ... 12)