Electrical installation

Power connections

Connection to the DC bus (+U

G

, −U

G

)

4

l

57

EDKCSDK002 DE/EN/FR 1.1

4.2.1

Connection to the DC bus (+U

G

, −U

G

)

ƒ

With a total cable length of > 20 m, install an axis module or a capacitor
module directly at the power supply module.

ƒ

Twist ±U

G

cables and keep the cable length as short as possible. Pay

attention to short−circuit−proof installation!

ƒ

Cable length > 30 cm:

Shield ±U

G

cables.

Fuses

ƒ

When ECS series supply modules with a mains−side protection are used, the
DC−bus supply does not need to be fused.

ƒ

When Lenze devices of the 82xx and 93xx series are used in DC−bus
connections with a continuous DC current > 40 A, install the following fuses:

Fuse

Holder

Value [A]

Lenze type

Lenze type

50

EFSGR0500ANIN

EFH20007

K

Warnings!

ƒ

Use UL−approved cables, fuses and fuse holders only.

ƒ

UL fuse:
– Voltage 500 ... 600 V
– Tripping characteristic "H", "K5" or "CC"

Cable cross−sections

Cable length

1)

Wire end ferrule

Cable
cross−section

Tightening torque

Stripping
length

Up to 20 m

Without wire end ferrule

6 mm

2

(AWG 10)

1.2 ... 1.5 Nm

(10.6 ... 13.3 lb−in)

5 mm

With wire end ferrule

> 20 m

Without wire end ferrule

10 mm

2

(AWG 8)

With wire end ferrule

l

Use pin−end connectors for
wiring!

1)

Cable length from module to module