Wiring according to EMC (installation of a CE−typical drive system)

4

l

54

EDKCSDK002 DE/EN/FR 1.1

Shielding

ƒ

Connect the motor cable shield to the axis module

with the shield mounting kit ECSZS000X0B001.

to the mounting plate below the axis module with a large surface.

Recommendation: For the shield connection, use earthing clamps on bare
metal mounting surfaces.

ƒ

If contactors, motor−protecting switches or terminals are located in the
motor cable:

Connect the shields of the connected cables and connect the shields to the
mounting plate, too, with a surface as large as possible.

ƒ

Connect the shield in the motor terminal box or on the motor housing to PE:

Metal glands at the motor terminal box ensure a large−surface connection
of the shield and the motor housing.

ƒ

Shield the control cables:

Connect both shield ends of the digital control cables.

Connect one shield end of the analogue control cables.

Always connect the shields to the shield connection at the axis module
over the shortest possible distance.

ƒ

Using the axis modules in residential areas:

Additionally dampen the shield in order to limit the interfering
radiation:

≥ 10 dB. This can be realised by using standard, closed, metallic,

and earthed control cabinets or boxes.

Earthing

ƒ

Earth all metallically conductive components (e. g. power supply module,
capacitor module, axis module, RFI filter, motor filter, mains choke) using
suitable cables connected to a central point (PE bar).

ƒ

Maintain the minimum cross−sections prescribed in the safety regulations:

For the EMC, not the cable cross−section is important, but the cable surface
and the contact with a surface as large as possible.