3 mechanical installation, 1 important notes, Mechanical installation – Lenze ECSDKxxx User Manual

Page 47: Important notes

Advertising
background image

Mechanical installation

Important notes

3

l

47

EDKCSDK002 DE/EN/FR 1.1

3

Mechanical installation

3.1

Important notes

ƒ

Capacitor modules of series ECS feature enclosure IP20 and, for this reason,
are intended for installation in control cabinets.

ƒ

If the cooling air contains air pollutants (dust, fluff, grease, aggressive gases):

Take suitable preventive measures , e.g. separate air duct, installation of
filters, regular cleaning.

ƒ

Possible mounting positions

Vertical on the mounting plate

DC−bus connections (X23) at the top

Connection for short−circuiting of the charging current limitation (X26) at
the bottom

ƒ

Maintain the specified free spaces above and below to other installations!

An additional free space is required if the shield assembly set
ECSZS000X0B001 is used.

Ensure unimpeded ventilation of cooling air and outlet of exhaust air.

You can install several modules of series ECS next to each other without
any clearance in a control cabinet.

ƒ

The mounting plate of the control cabinet must be electrically conductive.

ƒ

In case of continuous vibrations or shocks use shock absorbers.