Mechanical installation

3.1

Important notes

ƒ

Capacitor modules of series ECS feature enclosure IP20 and, for this reason,
are intended for installation in control cabinets.

ƒ

If the cooling air contains air pollutants (dust, fluff, grease, aggressive gases):

–

Take suitable preventive measures , e.g. separate air duct, installation of
filters, regular cleaning.

ƒ

Possible mounting positions

–

Vertical on the mounting plate

–

DC−bus connections (X23) at the top

–

Connection for short−circuiting of the charging current limitation (X26) at
the bottom

ƒ

Maintain the specified free spaces above and below to other installations!

–

An additional free space is required if the shield assembly set
ECSZS000X0B001 is used.

–

Ensure unimpeded ventilation of cooling air and outlet of exhaust air.

–

You can install several modules of series ECS next to each other without
any clearance in a control cabinet.

ƒ

The mounting plate of the control cabinet must be electrically conductive.

ƒ

In case of continuous vibrations or shocks use shock absorbers.