Technical Data

UOOu_^MTMO

3-3

L

3.2.2

Types 8225 to 8227

150 % overload

Type

8225

8226

8227

Order no.

EVF8225-E

EVF8226-E

EVF8227-E

Mains voltage

V

N

[V]

320 V - 0% ≤ V

N

≤528 V + 0% ; 45 Hz ¼ 65 Hz 0%

Alternative DC supply

V

G

[V]

460 V - 0% ≤ V

G

≤ 740 V + 0%

Mains current
with mains filter/mains choke
without mains filter/mains choke

I

mains

[A]

I

mains

[A]

100

--

135

--

165

--

Data for mains operation with 3 AC/400 V/50 Hz/60 Hz ; 460 V ≤ V

G

≤ 725 V or 3 AC/480 V/50 Hz/60 Hz ; 460 V ≤ V

G

≤ 765 V

400 V

480 V

400 V

480 V

400 V

480 V

Motor power (4 pole ASM)

4 kH /8 kH *

P

N

[kW]

55

75

75

90

90

110

p

( p

)

at 4 kHz/8 kHz*

P

N

[hp]

74

100

100

120

120

148

Output power U, V, W

at 4kHz/8 kHz*

S

N8

[kVA]

76.2

91.4

103.9

124

124.7

149

Power output +U

G

, -U

G

1)

P

DC

[kW]

0

0

28.1

32.4

40.8

47.1

Output

4 kHz*

I

N4

[A]

110

105

150

142

180

171

p

current

8 kHz*

I

N8

[A]

110

105

150

142

171

162

12 kHz*

I

N12

[A]

88

83

120

112

126

117

16 kHz*

I

N16

[A]

77

72

105

98

108

99

noise optimized 12 kHz*

I

N12

[A]

66

60

82

75

90

81

noise optimized 16 kHz*

I

N16

[A]

60

55

67

60

72

63

Max.

4 kHz*

I

Nmax4

[A]

165

157

225

213

270

256

output

current

8 kHz*

I

Nmax8

[A]

165

157

225

213

221

211

current

for 60s

2)

12 kHz*

I

Nmax12

[A]

114

108

156

147

164

153

for 60s

2)

16 kHz*

I

Nmax16

[A]

100

94

136

128

140

130

noise optimized 12 kHz*

I

Nmax12

[A]

85

78

107

98

117

106

noise optimized 16 kHz*

I

Nmax16

[A]

78

72

87

78

94

83

Motor voltage

3)

V

M

[V]

0 - 3 ×V

mains

/ 0Hz

¼ 50Hz, selectable up to 480Hz

Power loss (operation with I

Nx

)

P

v

[W]

1470

1960

2400

Power derating

[%/K]

[%/m]

40

°C < T

amb

< 50

°C: 2.5%/K

1000 m amsl < h ≤ 4000 m amsl: 5%/1000m

Field

f

Resolution

absolute

0.02 Hz

frequency Digital setpoint selection

Accuracy

0.05 Hz

Analog setpoint selection

Linearity

0.5 % (max. selected signal level: 5 V or 10 V)

g

p

Temperature

sensitivity

0

¼ 40 °C: +0.4 %

Offset

0 %

Weight

m [kg]

36.5

59

59

Printed in bold: Data for the operation with factory setting and a chopper frequency of 8 kHz.

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned
here and 2 minutes base load with 75% I

Nx

3)

With mains choke/mains filter: max. output voltage = ca. 96 % of the mains voltage

*

Chopper frequency of the inverter