3 adapt machine data, 1 determine speed range (fdmin, fdmax), Adapt machine data – Lenze 8240 frequency inverters User Manual

Page 35: Determine speed range (fdmin, fdmax), Commissioning, 1 determine speed range (f

Advertising
background image

Commissioning

UOOu_^MTMO

5-3

L

5.3

Adapt machine data

5.3.1

Determine speed range (f

dmin,

f

dmax)

Code

Name

Possible settings

IMPORTANT

Lenze

Selection

Info

C010 Minimum field

frequency

0.0

0.0

{0.1Hz}

480.0

C011 Maximum field

frequency

50.0

7.5

{0.1Hz}

480.0

Function

The speed range required for the application can be selected here by determing the field

frequencies f

dmin

and f

dmax

:

D

f

dmin

corresponds to the speed at 0 % speed setpoint selection.

D

f

dmax

corresponds to the speed at 100 % speed setpoint selection.

Adjustment

Relation between field frequency and synchronous motor speed:

е

клуе

=

С

Зг~с

⋅ SM

é

n

rsyn

synchronous motor speed [min

-1

]

f

dmax

max. field frequency [Hz]

p

number of pole pairs

Example: 4 pole asynchronous motor:
p = 2, f

dmax

= 50 Hz

е

клуе

=

RM ⋅ SM

O

= NRMM ãáå

ÓN

Important

D

With the setting of f

dmin

> f

dmax

the field frequency is limited to f

dmax

.

D

When selecting the setpoint by means of JOG values, f

dmax

acts as limitation.

D

f

dmax

is and internal standardization variable:

- Use the LECOM interface only for important modifications, when the controller is inhibited.

D

Observe the maximum speed of the motor!

D

f

dmin

is only effective under the following conditions:

- With analog setpoint selection.
- With the motor potentiometer function ”DOWN”.

Special features

D

With field frequencies f

d

> 300Hz:

- Avoid chopper frequencies < 8 kHz.

D

With C500 and C501, you can relate the display value of f

dmin

and f

dmax

to a process value.

fd

C011
(fdmax)

C010
(fdmin)

0 %

100 %

Show/Hide Bookmarks