Troubleshooting and fault elimination

UOOu_^MTMO

8-5

L

8.4

Reset of fault indications

TRIP

^СнЙк Йдбгбе~нбеЦ нЬЙ С~ìäíI нЬЙ ймдлЙ беЬбДбн пбдд зеду ДЙ кЙлЙн ~СнЙк нЬЙ
~ЕвезпдЙЗЦЙгЙен зС qofmK

Note!

fС нЬЙ qofm лзмкЕЙ бл лнбдд ~ÅíáîÉI íÜÉ qofm Е~еезн ДЙ êÉëÉíK

Code

Name

Possible settings

IMPORTANT

Lenze

Selection

Info

C170

¿ TRIP-reset selection

-0-

TRIP-reset by pressing the STP key
or a LOW signal at ctrl. enable

-1-

Auto-TRIP reset

C171 Deceleration for

Auto-TRIP reset

0

0

{1s}

60

Function

You can select whether the active fault is to be reset automatically or manually.

Auto-Trip reset does not reset all faults automatically.

Activation

C170 = -0-:

D

Manual TRIP-reset

D

STP key

D

LOW signal at terminal 28

C170 = -1-:
Auto-Trip reset resets the following fault messages after the time set under C171:

- OC3 (overload during acceleration)
- OC4 (overload during deceleration)
- OC5 (overload)
- OC6 (I ¡ t switch-off)
- OH (overtemperature)
- OUE (overvoltage in DC bus)

Important

Mains switching always resets TRIP.
With more than 8 auto-trip resets within 10 minutes, the controller sets TRIP and indicates rST

(numerator exceeded).