Configuration – Lenze 8240 frequency inverters User Manual

Page 50

Advertising
background image

Configuration

7-6

UOOu_^MTMO

L

Code

IMPORTANT

Possible settings

Name

Code

IMPORTANT

Info

Selection

Lenze

Name

C119

¿ Function PTC

822X/824X

-0-

-0-

PTC input inactive

-1-

PTC input active,
TRIP and IMP (pulse inhibit) are set

-2-

PTC input active, warning

C120 I

2

¡ t switch off

822X/824X

0

0

{1 %}

100

C125

¿* LECOM baud rate

-0-

-0-

9600 baud

-1-

4800 baud

-2-

2400 baud

-3-

1200 baud

-4-

19200 baud

Only for LECOM
applications

C142

¿ Start condition

-1-

-0-

Automatic start inhibited,
flying-restart circuit inactive

-1-

Automatic start, if term. 28 HIGH,
flying-restart circuit not active

-2-

Automatic start inhibited,
flying-restart circuit active

-3-

Automatic start, if term. 28 HIGH,
flying-restart circuit active

C144

¿ Chopper-frequency

reduction

821X/822X/824X

-1-

-0-

No chopper-frequency reduction

-1-

Automatic chopper-frequency
lowering when

J

max

- 10

°C

C161* Current fault

Only display

C162* Last fault

Only display

C163* Last but one fault

Only display

C164* Last but two fault

Only display

C170

¿ TRIP-reset selection

-0-

TRIP-reset by pressing the STP key
or LOW signal at ctrl. enable

-1-

Auto-TRIP-Reset

C171 Delay for

Auto-TRIP-Reset

0

0

{1s}

60

C178* Operating time

Only display

C179* Mains switch-on

time

Only display

C377 Gain Zk-voltage

detection

822X/824X

Should only be

changed by the

Lenze Service!

C500* Display factor

application datum
numerator

821X/822X/824X

2000

1

{1}

25000

C501* Display factor for

process variable
denominator

821X/822X/824X

10

1

{1}

25000