3 types 8241 to 8243, Types 8241 to 8243, Technical data – Lenze 8240 frequency inverters User Manual

Page 12

Advertising
background image

Technical Data

3-4

UOOu_^MTMO

L

3.2.3

Types 8241 to 8243

150 % overload

Type

8241

8242

8243

Order no.

EVF8241-E

EVF8242-E

EVF8243-E

Variant ”Cold Plate”

Type

8241-V003

8242-V003

8243-V003

Order no.

EVF8241-C-V003

EVF8242-C-V003

EVF8243-C-V003

Mains voltage

V

N

[V]

320V 0% ≤ V

N

≤ 528V 0% ; 45Hz ¼ 65Hz 0%

Alternative DC supply

V

G

[V]

460V 0% ≤ V

G

≤ 740V 0%

Mains current
with mains filter/mains choke
without mains filter/mains choke

I

mains

[A]

I

mains

[A]

1.5
2.1

2.5
3.5

3.9
5.5

Data for mains operation with 3 AC/400 V/50 Hz/60 Hz ; 460 V ≤ V

G

≤ 725 V or 3 AC/480 V/50 Hz/60 Hz ; 460 V ≤ V

G

≤ 765 V

400 V

480 V

400 V

480 V

400 V

480 V

Motor power (4 pole ASM)

4 kH /8 kH *

P

N

[kW]

0.37

0.37

0.75

0.75

1.5

1.5

p

( p

)

at 4 kHz/8 kHz*

P

N

[hp]

0.5

0.5

1.0

1.0

2.0

2.0

Output power U, V, W

at 4kHz/8 kHz*

S

N8

[kVA]

1.0

1.2

1.7

2.1

2.7

3.2

Power output +U

G

, -U

G

1)

P

DC

[kW]

1.9

2.3

0.7

0.9

0

0

Output

4 kHz*

I

N8

[A]

1.5

1.5

2.5

2.5

3.9

3.9

p

current

8 kHz*

I

N8

[A]

1.5

1.5

2.5

2.5

3.9

3.9

12kHz*

I

N12

[A]

1.35

1.35

2.2

2.2

3.5

3.5

16 kHz*

I

N16

[A]

1.2

1.2

2.0

2.0

3.1

3.1

noise optimized 12 kHz*

I

N12

[A]

1.3

1.3

2.1

2.1

3.4

3.4

noise optimized 16 kHz*

I

N16

[A]

1.1

1.1

1.8

1.8

2.9

2.9

Max.

4 kHz*

I

Nmax8

[A]

2.2

2.25

3.7

3.75

5.8

5.85

output

current

8 kHz*

I

Nmax8

[A]

2.2

2.25

3.7

3.75

5.8

5.85

current

for 60s

2)

12 kHz*

I

Nmax12

[A]

2.0

2.0

3.3

3.3

5.2

5.2

for 60s

2)

16 kHz*

I

Nmax16

[A]

1.8

1.8

3.0

3.0

4.7

4.7

noise optimized 12 kHz*

I

Nmax12

[A]

1.9

1.9

3.2

3.2

5.1

5.1

noise optimized 16 kHz*

I

Nmax16

[A]

1.6

1.6

2.7

2.7

4.3

4.3

Motor voltage

3)

V

M

[V]

0 - 3 ×V

mains

/ 0Hz

¼ 50Hz, selectable up to 480Hz

Power loss (operation with I

Nx

)

P

v

[W]

50

65

100

Power derating

[%/K]

[%/m]

40

°C < T

amb

< 50

°C: 2.5%/K

1000 m amsl < h ≤ 4000 m amsl: 5%/1000m

Field

f

Resolution

absolute

0.02 Hz

frequency Digital setpoint selection

Accuracy

0.05 Hz

Analog setpoint selection

Linearity

0.5 % (max. selected signal level: 5 V or 10 V)

g

p

Temperature

sensitivity

0

¼ 40 °C: +0.4 %

Offset

0 %

Weight
”Cold Plate” without heat sink

m [kg]

3.5

3.5

5.0

Printed in bold: Data for the operation with factory setting and a chopper frequency of 8 kHz.

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned
here and 2 minutes base load with 75% I

Nx

3)

With mains choke/mains filter: max. output voltage = ca. 96 % of the mains voltage

*

Chopper frequency of the inverter

Show/Hide Bookmarks

Advertising
This manual is related to the following products: