Troubleshooting and fault elimination

8-4

UOOu_^MTMO

L

Display

Remedy

Cause

Fault

OV

Overvoltage

Mains voltage too high

Check voltage supply

g

Feedback operation
Braking operation

D

Increase deceleration times.

D

For operation with brake choppers:

- Check the selection and connection of the

brake resistor

- Increase the deceleration times

Earth leakage on the motor side

Check motor cable and motor for earth fault

(disconnect motor from inverter)

rSt

Faulty auto-TRIP reset

More than 8 fault messages in

10 minutes

Depends on the fault message

Pr

Faulty parameter transfer via

the operating module

PAR1 and PAR2 are defective.

It is absolutely necessary to repeat the data

transfer or load the factory setting before

Pr1

Faulty PAR1 transfer via the

operating module

PAR1 is defective.

y

g

enabling the controller.

Pr2

Faulty PAR2 transfer via the

operating module

PAR2 is defective.