Commissioning

UOOu_^MTMO

5-9

L

5.4.2.2

Optimize V/f-characteristic control

Codes required

Code

Name

Possible settings

IMPORTANT

Lenze

Selection

Info

C015 V/f-rated frequency

50.0

7.5

{0.1Hz}

960.0

C016 V

min

setting

0

0

{1 %}

40

C021 Slip compensation

0

0

{1 %}

20

Setting sequence
1.If necessary, select V/f

characteristic (C014).

2.Select V/f-rated frequency

(C015).

D

The V/f-rated frequency determines the slope of the V/f characteristic and has considerable
influence on the current, torque and power performance of the motor.

D

An internal mains voltage compensation compensates deviations in the mains during operation.
They therefore do not have to be considered for the setting of C015.

Adjustment
Calculate the frequency to be set under C015

`MNR xeòz =

QMMs

r

к~нЙЗ гзнзк

xsz ⋅

o~нЙЗ гзнзк СкЙимЙеЕу xeòz

C014 = -2-

Linear characteristic

C014 = -3-

Square-law characteristic (e. g. for pumps, fans)

V

out

V

ratedmotor

1

V

min

0

0

1

C015

f

dratedmotor

V

min

0

0

1

V

out

V

ratedmotor

C015

f

dratedmotor