Assignment of the control terminals

62

7

8

9

K11

K12

K14

20

28

E1

E2

E3

E4

39

K21

K22

K24

Protection against contact
The control terminals have a basic isolation (double insulating distance). The protection

against contact is ensured without any additional measures.
Protection against polarity reversal
The protection against polarity reversal prevents the wrong connection of the internal

control inputs. It is however possible to overcome the protection against polarity reversal
by applying great force.
Motor-temperature monitoring
The connections of the motor-temperature monitoring (T1, T2) are next to the connection
terminals U, V, W.

cfd QJV

mçëáíáçå зС нЬЙ Езенкзд нЙкгбе~дл

Terminal

Use
(Factory setting is printed in bold)

Level

Data

Analog

7

GND 1

g

inputs

8

Setpoint input,

reference:
Terminal 7
(0 to 10V)

6

4

2

5

3

1

5 - 6
5 - 6
3 - 4
1 - 2

0 to 20 mA
4 to 20 mA
0 to 5 V
0 to 10 V

Resolution: 10 bit
Linearity fault:

±0.5 %

Temperature fault: 0.3 % (0...+40

°C)

Input resistance
Voltage signal: > 100 kΩ

Jumper

Voltage signal: > 100 kΩ
Current signal: 250 Ω

9

Supply for setpoint potentiometer

5.2V / 6mA

Analog
output

62

Analog output, reference: terminal 7
(Field frequency)

0... 6 V / 2 mA Resolution: 10 bit

Digital

inputs

20

Voltage supply for digital inputs
15 V/20 mA

p

28

Controller enable

HIGH

HIGH:

12 V ... 30 V

E4

CW rotation/
CCW rotation (CW/CCW)

CW: LOW
CCW: HIGH

LOW:

0 V ... 3 V

E3

DC-injection brake

HIGH

E2

JOG frequencies

Binary code

E1

q

20Hz, 30Hz, 40Hz

y

39

GND 2 (reference for external voltages)

Monitoring T1

Motor-temperature monitoring
(PTC thermistor/thermal contact)

If not used: set parameter C119 = -0-!

T2

Motor-temperature monitoring
(PTC thermistor/thermal contact)

Terminal

Use
(Factory setting is printed in bold)

Relay position (switched)

Data

Relay

output K1

K 11

Relay output normally-closed contact
(TRIP)

opened

24 V AC / 3,0 A or
60 V DC / 0.5 A

p

K 12

Relay mid-position contact

K 14

Relay output normally-open contact
(TRIP)

closed

Relay

output K2

K 21

Relay output normally-closed contact
(Ready for operation)

opened

250 V AC / 3,0A or
60 V DC / 0.5A

p

K 22

Relay mid-position contact

250 V AC / 3,0A or
60 V DC / 0.5A

K 24

Relay output normally-open contact
(Ready for operation)

closed

250 V AC / 3,0A or
60 V DC / 0.5A