Commissioning

5-2

UOOu_^MTMO

L

5.2

Short set-up with factory setting

5.2.1

Switch-on sequence

Step
1.Switch on mains voltage
2.Select the direction of rotation.

D

CW rotation:

- Apply a LOW signal to terminal E4 (0...+3V).

D

CCW rotation:

- Apply a HIGH signal to terminal E4 (+12...+30V).

3.Select the setpoint.

Apply a voltage 0...+10 V to terminal 8.

4.Enable the controller.

Apply a HIGH signal (+12...+30V) to terminal 28.

5.The drive is now operating according to factory setting.

5.2.2

Factory setting of the most important drive parameters

Setting

Code

Factory setting

Adaption to

the application

Operating mode

C001

-0-

Setpoint selection via terminal 8
Control via terminals
Parameter setting via 8201BB

See the Code

Table

chapter 7.2

Terminal configuration

C007

-0-

E4

E3

E2

E1

CW/CCW DC brake

JOG1/2/3

See the Code

Table

chapter 7.2

Machine data

Chapter 5.3 ff.

Speed range

Min. field frequency

C010

0.0 Hz

See chapter

p

g

Max. field frequency

C011 50.0 Hz

p

5.3.1

Acceleration and
deceleration

Acceleration time

C012

5.0 s

See chapter
5 3 2

deceleration
times

Deceleration time

C013

5.0 s

5.3.2

Current limit

Motor mode

C022

150 %

See chapter

values

Generator mode

C023

80 %

p

5.3.3

Drive performance

Chapter 5.4 ff.

Current,
torque

Operating mode

C014

-4-

Motor-current control

Motor-current
control see

torque,
power

V/f rated frequency

C015 50.0 Hz

control, see
chapter 5.4.2.1

power
characteristic

V

min

setting

C016

0 %

c apte 5
V/f characteristic
control see

Slip compensation

C021

0 %

control, see
chapter 5.4.2.2