3 rated data (operation wih 120 % overload), 1 operating conditions, 2 types 822x – Lenze 8240 frequency inverters User Manual

Page 14: 3 types 824x, Rated data (operation wih 120 % overload), Operating conditions, Types 822x, Types 824x, Technical data

Advertising
background image

Technical Data

3-6

UOOu_^MTMO

L

3.3

Rated data (operation wih 120 % overload)

3.3.1

Operating conditions

D

^ййдбЕ~íáçåëW
J mìãéë пбнЬ лим~кЙ ЕЬ~к~ЕнЙкблнбЕ
J c~åë

D

léÉê~нбзе зеду
J пбнЬ г~бел СбднЙк зк г~бел ÅÜçâÉK
J пбнЬ ~ г~бел оздн~ЦЙ зС P ^` L QMM s L RM eòLSM eòK

D

^мнзг~нбЕ ÅÜçééÉêJÑêÉèìÉåÅó ЗЙк~нбеЦ нз Q âeòK

D

^З~йн г~áåëJëáÇÉ ~ЕЕЙллзкбЙл нз нЬЙ беЕкЙ~лЙЗ г~бел ÅìêêÉåíW
J cзк СмлЙл ~еЗ Е~ДдЙ ÅêçëëJëÉÅíáçåë лЙЙ ЕЬ~йнЙк PKQKPK
J cзк З~н~ зС знЬЙк ЕзгйзеЙенл лЙЙ Т^ÅÅÉëëçêáÉëÒK

3.3.2

Types 822X

120 % overload

Type

8221

8222

8223*

8224

8225*

8226

8227*

Mains current
with mains filter/mains choke

I

mains

[A]

39.0

50.0

60.0

97.0

119

145

185

Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ V

G

≤ 725 V

Motor power (4-pole ASM)

P

N

[kW]

22

30

37,5

55

75

90

110

p

( p

)

P

N

[hp]

30

40

50

74

100

120

148

Output power U, V, W

S

N4

[kVA]

29.8

39.5

46.4

74.8

91.5

110

142

Output current

I

N4

[A]

43

56

66

100

132

159

205

Max. output current for für 60s

I

Nmax4

[A]

50

70.5

89

134

165

225

270

Power loss (operation with I

N4

)

P

v

[W]

640

810

810

1350

1470

2100

2400

*

Max. permissible ambient operating temperature + 35

°C

For other data see chapter 3.2.1 and chapter 3.2.2.

3.3.3

Types 824X

120 % overload

Type

8241

8242

8243

8244

8245

8246

Mains current
With mains choke

I

mains

[A]

1.7

2.8

5.0

8.8

15.0

20.5

Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V ≤ V

G

≤ 725 V

Motor power (4-pole ASM)

P

N

[kW]

0.55

1.1

2.2

4.0

7.5

11.0

p

( p

)

P

N

[hp]

0.75

1.5

2.9

5.4

10.0

15.0

Output power U, V, W

S

N4

[kVA]

1.3

2.1

3.8

6.5

11.1

16.3

Output current

I

N4

[A]

1.8

3.1

5.5

9.2

16.0

23.5

Max. output current for für 60s

I

Nmax4

[A]

2.25

3.75

6.6

11.0

19.5

35.3

Power loss (operation with I

Nx

)

P

v

[W]

50

65

115

165

260

360

For other data see chapter 3.2.3 and chapter 3.2.4.