Fault indications

Display

Fault

Cause

Remedy

---

No fault

-

-

EEr

External fault (TRIP-Set)

A digital input assigned to the TRIP-Set

function has been activated

Check external encoder

H05

Internal fault

Contact Lenze

LU

Undervoltage

DC-bus voltage too low

D

Check mains voltage

D

Check supply module

OC1

Short circuit

Short circuit

Find out cause of short circuit; check cable

Excessive capacitive charging current

of the motor cable

Use motor cable which is shorter or of lower

capacitance

OC2

Earth fault

Grounded motor phase

Check motor; check cable

Excessive capacitive charging current

of the motor cable

Use motor cable which is shorter or of lower

capacitance

OC3

Overload inverter during

acceleration or short circuit

Acceleration time too short (C012)

D

Increase acceleration time

D

Check drive selection

Defective motor cable

Check wiring

Interturn fault in the motor

Check motor

OC4

Overload controller during

deceleration

Deceleration time too short (C013)

D

Increase deceleration time

D

Check the selection of the brake resistor or
connect the brake chopper

OC5

I x t overload

Frequent and too long acceleration

processes with overcurrent

Check drive dimensioning

Permanent overload with

I

motor

> 1.05 x I

Nx

OC6

Overload motor

Motor is thermally overloaded, for

instance, because of

D

impermissible continuous current

D

Check drive selection

D

frequent or too long acceleration
processes

D

Check the setting under C120

OH

Heat sink temperature is higher

than the value set in the

controller

Ambient temperature

T

amb

> +40

°C or +50 °C

D

Allow controller to cool and ensure
ventilation

D

Check the ambient temperature in the
control cabinet

Heat sink very dirty

Clean heat sink

Incorrect mounting position

Change mounting position

OH3

PTC monitoring (TRIP)

Motor too hot because of excessive

current or frequent and too long

acceleration

Check drive dimensioning

PTC not connected

Connect PTC or switch off monitoring

(C0585=3)

OH4

Overtemperature unit

Inside unit too hot

D

Reduce controller load

D

Improve cooling

D

Check fan in the controller

OH51

PTC monitoring (Warning)

Motor too hot because of excessive

current or frequent and too long

acceleration

Check drive selection

PTC not connected

Connect PTC or switch off monitoring

Show/Hide Bookmarks