Lenze 13466187 EDBTL03 v8

EN, DE, FR, IT, ES

9

Installation

Type

Installation to EN 60204-1

Installation to UL

E.l.c.b.

(2)

Fuse

Miniature

circuit

breaker

L1, L2, L3,

PE [mm²]

Fuse

(3)

L1, L2, L3,

PE [AWG]

ETML251X2SFA

ETML371X2SFA

ETML551X2SFA

M10 A

C10 A

1.5

10 A

14

> 30 mA

ETML751X2SFA

M16 A

C16 A

2.5

15 A

14

ETML112X2SFA

M20 A

C20 A

2.5

20 A

12

ETML152X2SFA

M25 A

C25 A

2.5

25 A

12

ETML222X2SFA

M30 A

C30 A

4.0

30 A

10

(1) Observe the applicable local regulations

(2) Pulse-current or universal-current sensitive earth leakage circuit breaker

(3) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, required. Bussman KTK-R, JJN, JJS, or equivalent

Observe the following when using E.l.c.b:

Installation of E.l.c.b only between supplying mains and controller.

The E.l.c.b can be activated by:

- apacitive leakage currents between the cable screens during operation (especially with

long, screened motor cables)

- connecting several controllers to the mains at the same time

- RFI filters

EMC

Compliance with EN 61800-3/A11

Noise emission

Drive models ending in the suffix “SFA” are in compliance with limit value class A

according to EN 55011 if installed in a control cabinet and with a motor cable not

longer than 10m.

A Screen clamps
B Control cable

C Low-capacitance motor cable

(core/core < 75 pF/m, core/screen < 150 pF/m)

D Electrically conductive mounting plate

Tml005

B

C

D

A

3.2

Electrical installation

3.2.1 Installation according to EMC requirements

3.2.2 Fuses/cable cross-sections

(1)