Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze Selection

C18

Chopper frequency

2

0 4 kHz

• As chopper frequency is increased,

motor noise is decreased

• Observe derating in Section 2.2

• C18 = 1, 2, 3: Automatic derating to

4 kHz at 1.2 x I

N

1 6 kHz
2 8 kHz
3 10 kHz

C21

Slip compensation

0.0

0.0 {%} 40.0

C21 not active in Vector mode (see C14)

Change C21 until the motor speed no

longer changes between no load and

maximum load

C22

Current limit

200

30 {%} 200

Reference: Tml rated output current

• When the limit value is reached,

either the acceleration time

increases or the output frequency

decreases

• When c73 = 0, max setting is 167%

C24

Accel boost

0.0

0.0 {%} 20.0

Accel boost is only active during

acceleration

C34

Configuration -

analog input

0

0 0...10 V
1 0...5 V
2 Reserved
3 0...20 mA

• With 250 Ω resistance between

terminals 7 and 8

• C34 = 5 will trigger 5d5 fault if

signal falls below 2 mA

4 4...20 mA
5 4...20 mA monitored

C36

Voltage - DC injection

brake (DCB)

4.0

0.0 {%} 50.0

• See CE1...CE3 and c06

• Confirm motor suitability for use

with DC braking

C37

Fixed setpoint 1

(JOG 1)

20.0

0.0 {Hz} 240 Lenze setting: active at E1 = HIGH

C38

Fixed setpoint 2

(JOG 2)

30.0

0.0 {Hz} 240 Lenze setting: active at E2 = HIGH

C39

Fixed setpoint 3

(JOG 3)

40.0

0.0 {Hz} 240 Lenze setting: active at E1 = HIGH

and E2 = HIGH

C46

Frequency setpoint

0.0 {Hz} 240 Display: Setpoint via analog input,

function UP/DOWN

C47

Torque setpoint/range

100

0 {%} 400 • When C14 = 5 and C01 = 1, 3, 5, 7

sets the torque setpoint

• When C14 = 5 and C01 = 0, 2, 4, 6

sets the torque range for C34

C50

Output frequency

0.0 {Hz} 240 Display

C52

Motor voltage

0 {V} 999 Display

C53

DC bus voltage

0 {V} 999 Display

C54

Motor current

0.0 {A} 400 Display

C56

Controller load

0 {%} 255 Display

C57

Motor torque

0 {%} 400 Display: vector mode only

(C14 = 4, 5)

C65

Vector speed control

loop gain

30.0

0.0 100 Optimizes dynamic performance in

vector mode

C66

Vector speed stability

30.0

0.0 100 Optimizes steady-state speed stability

in vector mode