Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze Selection

CE1

Configuration -

Digital input E1

1

1 Activate fixed setpoint 1 (JOG1)

Activate JOG3: Both terminals = HIGH

2 Activate fixed setpoint 2 (JOG2)

3 DC braking (DCB)

see also C36

4 Direction of rotation

LOW = CW rotation

HIGH = CCW rotation

5 Quick stop

Controlled deceleration to standstill,

active LOW; Set decel rate in C13

or c03

6 CW rotation

CW rotation = LOW and CCW rotation

= LOW: Quick stop; Open-circuit

protected

CE2

Configuration -

Digital input E2

2

7 CCW rotation

8 UP (setpoint ramp-up)

9 DOWN (setpoint ramp-down)

UP = LOW and DOWN = LOW: Quick

stop; Use momentary NC contacts

10 TRIP set

Active LOW, triggers

EEr

(motor

coasts to standstill)

NOTE: NC thermal contact from the

motor can be used to trigger this input

11 TRIP reset

see also c70

12 Accel/decel 2

see c01 and c03

CE3

Configuration -

Digital input/output E3

3

1…12 (same as above)

13...19 (reserved)

20 Ready

21 Fault

22 Motor is running

23 Motor is running - CW rotation

24 Motor is running - CCW rotation

25 Output frequency = 0Hz

26 Frequency setpoint reached

27 Frequency threshold (C17) exceeded

28 Current limit (motor or generator mode)

reached

29 Dynamic braking

• 1…12 configures terminal E3 as

an input.

• 20…29 configures terminal E3 as a

current-sourcing (PNP) output rated

12 VDC / 50 mA

Note
A

CFG

fault will occur under the following conditions:

• E1...E3 settings are duplicated (each setting can only be used once)

• One input is set to UP and another is not set to DOWN, or vice-versa

• When C01 = 4...7, terminals E2 and E3 must be used for the remote keypad, selections

made for CE2 and CE3 will be ignored.

C08

Configuration - Relay

output (terminals K14

and K12

1

Relay is energized if

0 Ready

1 Fault

2 Motor is running

3 Motor is running - CW rotation

4 Motor is running - CCW rotation

5 Output frequency = 0Hz

6 Frequency setpoint reached

7 Frequency threshold (C17) exceeded

8 Current limit (motor or generator mode)

reached