Commissioning, 3 parameter menu – Lenze TML Flux Vector Drive 0.25kW-2.2kW User Manual

Page 15

Advertising
background image

Lenze 13466187 EDBTL03 v8

EN, DE, FR, IT, ES

13

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze Selection

C00

Password entry

0

0 999 Visible only when password is active

(see C94)

C01

Setpoint and control

source

0

Setpoint source:

Control configuration:

0 Analog input (terminal 8; see C34)

Control = terminals

Programming = keypad

1 Code c40 / Code C47

2 Analog input (terminal 8; see C34)

3 Code c40 / Code C47

4 Analog input (terminal 8; see C34)

Control = terminals

Programming = remote keypad

Monitoring = remote keypad

5 Code c40 / Code C47

6 Analog input (terminal 8; see C34)

Control = remote keypad

Programming = remote keypad

Monitoring = remote keypad

7 Code c40 / Code C47

Note

• When C01 = 1, 3, 5, or 7 and C14 = 0...4, 6, 7, use c40 for speed setpoint

• When C01 = 1, 3, 5, or 7 and C14 = 5, use C47 for torque setpoint

• When C01 = 4...7, terminals E2 and E3 must be used for the remote keypad,

selections made for CE2 and CE3 will be ignored.

C02

Load Lenze setting

0 No action/loading complete

• C02 = 1, 2, 3 only possible with

OFF

or

1nh

• C02 = 2 : C11, C15 and C89 = 60

Hz and C87 = 1750RPM

1 Load 50 Hz Lenze settings

2 Load 60 Hz Lenze settings

3 Load OEM settings (if present)

WARNING!

C02 = 1...3 overwrites all settings! TRIP circuitry may be disabled! Check codes CE1...

CE3.

4.3

Parameter menu