Safety information – Lenze TML Flux Vector Drive 0.25kW-2.2kW User Manual

Page 7

Advertising
background image

Lenze 13466187 EDBTL03 v8

EN, DE, FR, IT, ES

5

Safety information

Note for UL approved system with integrated controllers

UL warnings are notes which apply to UL systems. The documentation contains special information

about UL.

Warnings!

• Integral solid state protection does not provide branch circuit protection. Branch

circuit protection must be provided in accordance with the National Electrical

Code and any additional local codes. The use of fuses or circuit breakers is

the only approved means for branch circuit protection.

• When protected by CC and T Class Fuses, suitable for use on a circuit capable

of delivering not more than 200,000 rms symmetrical amperes, at the maximum

voltage rating marked on the drive.

• Additionally suitable when protected by a circuit breaker having an interrupting

rating not less than 200,000 rms symmetrical amperes, at the maximum voltage

rating marked on the drive.

• Use minimum 75°C copper wire only, except for control circuits.
• For control circuits, use wiring suitable for NEC Class 1 circuits only.
• Torque Requirements are listed in section 3.2.3, Connection diagram.
• Shall be installed in a pollution degree 2 macro-environment.

WARNING!

Risk of Electric Shock! Capacitors retain charge for approximately 180 seconds after

power is removed. Disconnect incoming power and wait at least 3 minutes before

touching the drive.

WARNING!

The opening of branch-circuit protective device may be an indication that a fault has

been interrupted. To reduce the risk of fire or electric shock, current carrying parts

and other components of the controller should be examined and replaced if damaged.