Installation, 4 control terminals – Lenze TML Flux Vector Drive 0.25kW-2.2kW User Manual

Page 13

Advertising
background image

Lenze 13466187 EDBTL03 v8

EN, DE, FR, IT, ES

11

Installation

Terminal Data for control connections

(printed in bold = Lenze setting)

7

Reference common

8

Analog input

0 … 10 V

(changeable under C34)

input resistance: >50 kΩ

(with current signal: 250 Ω)

9

Internal DC supply for setpoint potentiometer

+10 V, max. 10 mA

20

Internal DC supply for digital inputs

+12 V, max. 20 mA

28

Digital input Start/Stop

LOW = Stop; HIGH = Run Enable

input resistance = 3.3 kΩ

E1

Digital input configurable with CE1

Activate fixed setpoint 1 (JOG1)

HIGH = JOG1 active

Both HIGH = JOG3 active

R

i

= 3.3 k

E2

Digital input configurable with CE2

Activate fixed setpoint 2 (JOG2)

HIGH = JOG2 active

E3

Digital input configurable with CE3

Activate DC injection brake (DCB)

HIGH = DCB active

K14

Relay output (N.O. contact)

configurable with C08

Fault (TRIP)

AC 250V / 3A

DC 24V / 2A ... 240V / 0.22A

K12

LOW = 0 … +3 V, HIGH = +12 … +30 V

Protection against contact

• All terminals have a basic isolation (single insulating distance)

• Protection against contact can only be ensured by additional measures (i.e. double insulation)

3.2.4 Control terminals