Troubleshooting and fault elimination – Lenze TML Flux Vector Drive 0.25kW-2.2kW User Manual

Page 24

Advertising
background image

22

Lenze 13466187 EDBTL03 v8

EN, DE, FR, IT, ES

Troubleshooting and fault elimination

Error

Cause

Remedy

(1)

JF

Remote keypad fault

Remote keypad disconnected

Check remote keypad connections

n1d

Drive identification fault

Attempt was made to perform motor

calibration before setting C86...C91

Must set C86...C91 before performing

motor calibration (see c48)

0C1

Short-circuit or overload

Short-circuit

Find reason for short-circuit; check

motor cable

Excessive capacitive charging

current of the motor cable

Use shorter motor cables with lower

charging current

Acceleration time (C12, c01) too short

• Increase acceleration time

• Check controller selection

Defective motor cable

Check wiring

Internal fault in motor

Check motor

Frequent and long overload

Check controller selection

0C2

Earth fault

Grounded motor phase

Check motor/motor cable

Excessive capacitive charging

current of the motor cable

Use shorter motor cables with lower

charging current

0C6

Motor overload (I

2

t overload)

Motor is thermally overloaded, due to:

• impermissable continuous current

• frequent or too long acceleration

processes

• Check controller selection

• Check setting of c20

0H

Controller overtemperature

Controller too hot inside

• Reduce controller load

• Improve cooling

OU

Overvoltage on DC bus

Mains voltage too high

Check mains voltage

Excessively short deceleration time or

motor in generator mode

Increase deceleration time or use

dynamic braking option

Earth leakage on the motor side

Check motor/motor cable

(separate motor from controller)

rF

Flying restart fault

Controller was unable to synchronize

with motor during restart attempt

Check motor/load

rSt

Faulty auto-TRIP reset

More than 8 errors in 10 minutes

Depends on the error

Sd5

Loss of 4-20 mA reference

4-20 mA signal (terminal 8I) is below 2

mA (C34 = 5)

Check signal/signal wire

SF

Single phase fault

A mains phase has been lost

Check mains voltage

(1) The drive can only be restarted if the error message has been reset; see c70

NOTE

In the event of an “OC6” (Motor Overload) failure there is a 3-minute delay before resetting is possible.

This is a requirement of UL508C. This delay is intended to allow time for the motor to cool.
If power is removed when the drive is in an “OC6” fault state, when the power is restored the “OC6” fault

will still be present and the delay will still be active even if power was removed for longer than 3 minutes.

22

Lenze 13466187 EDBTL03 v8

EN, DE, FR, IT, ES